Generator Mode Detection
This page describes the health-state mapping for EnergyTrak Universal r5 Mode Detection and GMCM-A devices, which use generator mode detection.
Generator Health-State Mapping
The table below details how various states of your generator impact its overall health status. Rows are ordered top-to-bottom in reverse Health Color Priority — least severe first, most severe last.
State Mapping Table
| System | Health | State | Generator Mode | Description |
|---|---|---|---|---|
| Site | Healthy | Ready | Auto | Grid online and generator in standby; all systems are healthy and ready for grid outage. |
| Exercising | Auto | Grid online and the generator is running (assumed to be performing an exercise test). | ||
| Running | Auto | Grid offline and the generator is running (assumed to be powering the site). | ||
| Stopped | Auto | Grid offline and generator in standby. Generator is in Auto mode and ready to start. | ||
| Init | Ready | Init | Grid online and generator in standby. Mode detection is still initializing. | |
| Exercising | Init | Grid online and the generator is running. Mode detection is still initializing. | ||
| Running | Init | Grid offline and the generator is running. Mode detection is still initializing. | ||
| Stopped | Init | Grid offline and generator in standby. Mode detection is still initializing. | ||
| Notice | Manual | Manual | The generator is in manual mode and will not start automatically. | |
| Running | Manual | The generator is in manual mode and is running. | ||
| Stopped | Manual | Grid offline, generator in standby, in manual mode. The generator will not start automatically. | ||
| Warning | N/A | N/A | The site state is in warning (Low Generator Battery) and utility power is online. | |
| Critical | Fault | N/A | An active fault has been detected. | |
| Pending | Pending | N/A | Site is pending waiting for data from the device. | |
| Disconnected | Disconnected | N/A | Network connection to EnergyTrak has been lost. | |
| Deactivated | Deactivated | N/A | User has manually deactivated the site in the EnergyTrak app. | |
| Ready For Setup | Ready For Setup | N/A | Site has been created but setup has not been completed. | |
| Generator | Healthy | Standby | Auto | Generator is not producing power. |
| Running | Auto | Generator is producing voltage. | ||
| Init | Standby | Init | Smart Mode Detection is initializing. Generator is not producing voltage; mode and fault status are currently not available. | |
| Running | Init | Smart Mode Detection is initializing. Generator is producing voltage; mode and fault status are currently not available. | ||
| Notice | Manual | Manual | The generator is in manual mode and utility power is offline. | |
| Running | Manual | The generator is in manual mode but the generator is still running. | ||
| Warning | N/A | N/A | The generator state is in warning and utility power is online. | |
| Critical | Fault | Fault / Auto | A fault has been detected while the generator is in Auto mode. | |
| Fault | Fault / Manual | A fault has been detected while the generator is in Manual mode. | ||
| No Data | No Data | N/A | No Data when network state is disconnected OR site is not active. | |
| Grid | Healthy | Online | N/A | Grid voltage is present. |
| Warning | Offline | N/A | Grid voltage is not present. | |
| No Data | No Data | N/A | No Data when network state is disconnected OR site is not active. | |
| Network | Healthy | Connected | N/A | EnergyTrak device is connected. |
| Critical | Module Power Disconnected | N/A | EnergyTrak device has lost power. | |
| Disconnected | Disconnected | N/A | EnergyTrak device has not reported for more than 1 day. |