Generator Health-State Mapping

The table below details how various states of your generator impact its overall health status.

Table 1

Generator Health-State Mapping

SystemTypeHealthStateGenerator ModeSite Health ImpactDescription
SiteSiteHealthyReadyAutoN/AGrid online and generator in standby; all systems are healthy and ready for grid outage.
ExercisingAutoGrid online and the generator is running (assumed to be performing an exercise test).
RunningAutoGrid offline and the generator is running (assumed to be powering the site).
StoppedAutoGrid offline and generator in standby. Generator is in Auto mode and ready to start.
InitReadyUnknownN/AGrid online and generator in standby. Generator mode cannot be determined.
ExercisingUnknownGrid online and the generator is running. Generator mode cannot be determined.
RunningUnknownGrid offline and the generator is running. Generator mode cannot be determined.
StoppedUnknownGrid offline and generator in standby. Generator mode cannot be determined.
NoticeManualManualN/AThe generator is in manual mode and will not start automatically.
RunningManualN/AThe generator is in manual mode and is running.
StoppedManualN/AGrid offline, generator in standby, in manual mode. The generator will not start automatically.
WarningWarningN/AN/AThe site state is in warning (Low Generator Battery) and utility power is online.
CriticalFaultN/AN/AAn active fault has been detected.
DisconnectedDisconnectedN/AN/ANetwork connection to EnergyTrak has been lost.
DeactivatedDeactivatedN/AN/AUser has manually deactivated the site in the EnergyTrak app.
GeneratorEquipmentHealthyStandbyAutoHealthyGenerator is not producing power.
RunningAutoGenerator is producing voltage.
NoticeRunningManualNoticeThe generator is in manual mode but the generator is still running.
NoticeManualManualNoticeThe generator is in manual mode and utility power is offline.
WarningWarningN/AWarningThe generator state is in warning and utility power is online.
CriticalFaultN/ACriticalAn active fault has been detected.
InitStandbyUnknownInitGenerator mode cannot be determined. Amplify uses Unknown (not Init) when mode detection is unavailable.
No DataNo DataN/ANo ImpactNo Data when network state is disconnected OR site is not active.
GridEquipmentHealthyOnlineN/AHealthyGrid voltage is present.
WarningOfflineN/AWarningGrid voltage is not present.
No DataNo DataN/ANo ImpactNo Data when network state is disconnected OR site is not active.
NetworkEquipmentHealthyConnectedN/AHealthyEnergyTrak device is connected.
CriticalModule Power DisconnectedN/ACriticalEnergyTrak device has lost power.
DisconnectedDisconnectedN/ADisconnectedEnergyTrak device has not reported for more than 1 day.