Amplify
This page describes the health-state mapping for Amplify devices.
Smart Mode
Smart Mode is always enabled on Amplify devices and cannot be disabled. Because the mode is fixed, Smart Mode mismatch detection does not apply to Amplify.
Generator Health-State Mapping
The table below details how various states of your generator impact its overall health status.
Table 1
Generator Health-State Mapping
| System | Type | Health | State | Generator Mode | Site Health Impact | Description |
|---|---|---|---|---|---|---|
| Site | Site | Healthy | Ready | Auto | N/A | Grid online and generator in standby; all systems are healthy and ready for grid outage. |
| Exercising | Auto | Grid online and the generator is running (assumed to be performing an exercise test). | ||||
| Running | Auto | Grid offline and the generator is running (assumed to be powering the site). | ||||
| Stopped | Auto | Grid offline and generator in standby. Generator is in Auto mode and ready to start. | ||||
| Init | Ready | Unknown | N/A | Grid online and generator in standby. Generator mode cannot be determined. | ||
| Exercising | Unknown | Grid online and the generator is running. Generator mode cannot be determined. | ||||
| Running | Unknown | Grid offline and the generator is running. Generator mode cannot be determined. | ||||
| Stopped | Unknown | Grid offline and generator in standby. Generator mode cannot be determined. | ||||
| Notice | Manual | Manual | N/A | The generator is in manual mode and will not start automatically. | ||
| Running | Manual | N/A | The generator is in manual mode and is running. | |||
| Stopped | Manual | N/A | Grid offline, generator in standby, in manual mode. The generator will not start automatically. | |||
| Warning | Warning | N/A | N/A | The site state is in warning (Low Generator Battery) and utility power is online. | ||
| Critical | Fault | N/A | N/A | An active fault has been detected. | ||
| Disconnected | Disconnected | N/A | N/A | Network connection to EnergyTrak has been lost. | ||
| Deactivated | Deactivated | N/A | N/A | User has manually deactivated the site in the EnergyTrak app. | ||
| Generator | Equipment | Healthy | Standby | Auto | Healthy | Generator is not producing power. |
| Running | Auto | Generator is producing voltage. | ||||
| Notice | Running | Manual | Notice | The generator is in manual mode but the generator is still running. | ||
| Notice | Manual | Manual | Notice | The generator is in manual mode and utility power is offline. | ||
| Warning | Warning | N/A | Warning | The generator state is in warning and utility power is online. | ||
| Critical | Fault | N/A | Critical | An active fault has been detected. | ||
| Init | Standby | Unknown | Init | Generator mode cannot be determined. Amplify uses Unknown (not Init) when mode detection is unavailable. | ||
| No Data | No Data | N/A | No Impact | No Data when network state is disconnected OR site is not active. | ||
| Grid | Equipment | Healthy | Online | N/A | Healthy | Grid voltage is present. |
| Warning | Offline | N/A | Warning | Grid voltage is not present. | ||
| No Data | No Data | N/A | No Impact | No Data when network state is disconnected OR site is not active. | ||
| Network | Equipment | Healthy | Connected | N/A | Healthy | EnergyTrak device is connected. |
| Critical | Module Power Disconnected | N/A | Critical | EnergyTrak device has lost power. | ||
| Disconnected | Disconnected | N/A | Disconnected | EnergyTrak device has not reported for more than 1 day. |